34-46 107 Street, Queens

HPD violations

Housing Maintenance Code violations are filed by tax lot (BBL 4-01748-0031), so they can include other buildings on the same lot.

129 records

Date Class Status Apartment Summary
Feb 12, 2014 C VIOLATION CLOSED 2R § 27-2005 ADM CODE REPLACE WITH NEW THE MISSING AIR VALVE AT RADIATOR IN THE 3rd ROOM FROM EAST LOCATED AT APT 2R, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
Feb 12, 2014 B VIOLATION CLOSED 2R § 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 2R, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
Feb 12, 2014 B VIOLATION CLOSED 2R § 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 2R, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
Feb 12, 2014 C VIOLATION CLOSED 2R SECTION 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 2R, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
Feb 12, 2014 C VIOLATION CLOSED 2R SECTION 27-2028, 2032 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FROM AN APPROVED CENTRAL HEATING SYSTEM, OR AN APPROVED SYSTEM OF GAS OR ELECTRICAL HEATING IN GOOD OPERATING CONDITION FOR THE DWELLING UNIT IN THE ENTIRE APARTMENT LOCATED AT APT 2R, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
Jan 20, 2014 C VIOLATION CLOSED 1FL § 27-2031 ADMIN. CODE: PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 1FL, 1st STORY
Jan 20, 2014 C VIOLATION DISMISSED 1FL SECTION 27-2028, 2032 ADMIN.CODE: PROVIDE AN ADEQUATE SUPPLY OF HEAT FROM AN APPROVED CENTRAL HEATING SYSTEM OR AN APPROVED SYSTEM OF GAS OR ELECTRICAL HEATING IN GOOD OPERATING CONDITION FOR THE DWELLING UNIT IN THE ENTIRE APARTMENT LOCATED AT APT 1FL, 1st STORY
Dec 14, 2013 C VIOLATION CLOSED 2R § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FRAME FROM NORTH AT EAST WALL IN THE FOYER LOCATED AT APT 2R, 2nd STORY, 3rd APARTMENT FROM NORTH AT EAST
Dec 14, 2013 C VIOLATION CLOSED 2R § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) EAST WALL IN THE KITCHEN LOCATED AT APT 2R, 2nd STORY, 3rd APARTMENT FROM NORTH AT EAST
Dec 14, 2013 C VIOLATION CLOSED 2R § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FRAME FROM NORTH AT EAST WALL IN THE 2nd ROOM FROM EAST LOCATED AT APT 2R, 2nd STORY, 3rd APARTMENT FROM NORTH AT EAST
Dec 14, 2013 C VIOLATION CLOSED 2R § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st CLOSET FROM EAST AT SOUTH WALL DOOR, 1st DOOR FROM NORTH AT EAST WALL IN THE 3rd ROOM FROM EAST LOCATED AT APT 2R, 2nd STORY, 3rd APARTMENT FROM NORTH AT EAST
Dec 14, 2013 C VIOLATION CLOSED Not available § 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM - AT BOILER ROOM
Dec 14, 2013 B VIOLATION CLOSED 2R § 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE LOCK AT DOOR IN THE ENTRANCE LOCATED AT APT 2R, 2nd STORY, 3rd APARTMENT FROM NORTH AT EAST
Dec 14, 2013 B VIOLATION CLOSED 2R § 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 2R, 2nd STORY, 3rd APARTMENT FROM NORTH AT EAST
Dec 14, 2013 B VIOLATION CLOSED 2R § 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 2R, 2nd STORY, 3rd APARTMENT FROM NORTH AT EAST
Dec 14, 2013 C VIOLATION CLOSED 2R SECTION 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 6; WG TO REPLACE = 0; WG TO REPAIR = 0; IN THE ENTIRE APARTMENT LOCATED AT APT 2R, 2nd STORY, 3rd APARTMENT FROM NORTH AT EAST
Dec 14, 2013 C VIOLATION DISMISSED 2R SECTION 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 2R, 2nd STORY, 3rd APARTMENT FROM NORTH AT EAST
Dec 5, 2013 B VIOLATION CLOSED 2R § 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 2R, 2nd STORY, APARTMENT AT WEST
Dec 5, 2013 B VIOLATION CLOSED 2R § 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 2R, 2nd STORY, APARTMENT AT WEST
Dec 5, 2013 C VIOLATION CLOSED 2R SECTION 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 2R, 2nd STORY, APARTMENT AT WEST
Nov 26, 2013 C VIOLATION CLOSED Not available SECTION 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT BOILER ROOM
Nov 26, 2013 C VIOLATION CLOSED 1 SECTION 27-2028, 2032 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FROM AN APPROVED CENTRAL HEATING SYSTEM, OR AN APPROVED SYSTEM OF GAS OR ELECTRICAL HEATING IN GOOD OPERATING CONDITION FOR THE DWELLING UNIT IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY
Nov 6, 2013 A VIOLATION CLOSED Not available § 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX , AT PUBLIC HALL, 1st STORY
Nov 6, 2013 A VIOLATION CLOSED Not available § 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING. AT PUBLIC HALL, 1st STORY
Nov 6, 2013 C VIOLATION CLOSED 1 SECTION 27-2005 ADM CODE REPLACE WITH NEW THE MISSING RADIATOR IN THE 2nd ROOM FROM EAST LOCATED AT APT 1, 1st STORY
Nov 6, 2013 B VIOLATION CLOSED 1 § 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY
Nov 6, 2013 B VIOLATION CLOSED 1 § 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY
Nov 6, 2013 C VIOLATION CLOSED 1 SECTION 27-2028, 2032 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FROM AN APPROVED CENTRAL HEATING SYSTEM, OR AN APPROVED SYSTEM OF GAS OR ELECTRICAL HEATING IN GOOD OPERATING CONDITION FOR THE DWELLING UNIT IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY
Nov 6, 2013 C VIOLATION CLOSED 1 § 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY