| Date | Class | Status | Apartment | Summary |
|---|---|---|---|---|
| Jun 22, 2022 | C | VIOLATION CLOSED | Not available | § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD NEWL POST AND BALUSTRADE FROM CELLAR STAIRS LEADING TO 1STRY AT PUBLIC HALL STAIRS |
| Jun 22, 2022 | C | VIOLATION CLOSED | Not available | § 27-2005 ADM CODE PROVIDE A NEW APPROVED 1HR 1/2 FIRE RATED SELF CLOSING DOOR AT BOILER ROOM |
| Jun 22, 2022 | C | VIOLATION DISMISSED | Not available | § 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE AT BOILER ROOM |
| Jun 22, 2022 | C | VIOLATION CLOSED | Not available | § 27-2005 ADM CODE PROPERLY SECURE THE LOOSE NEWL POST AT HAND RAIL AT PUBLIC HALL, 3rd STORY |
| May 5, 2022 | B | NOT COMPLIED WITH | Not available | § 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS ON 2 STORY PUBLIC HALL |
| May 5, 2022 | A | VIOLATION CLOSED | Not available | § 27-2005 ADM CODE REFIT BUILDING ENTRANCE DOOR |
| May 5, 2022 | C | VIOLATION CLOSED | Not available | § 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE BUILDING ENTRANCE DOOR |
| May 5, 2022 | A | VIOLATION DISMISSED | Not available | § 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY |
| May 5, 2022 | A | VIOLATION DISMISSED | Not available | § 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING. |
| May 5, 2022 | A | VIOLATION DISMISSED | Not available | § 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX AT PUBLIC HALL, 1st STORY |
| May 5, 2022 | A | VIOLATION DISMISSED | Not available | § 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY |
| May 5, 2022 | A | VIOLATION DISMISSED | Not available | § 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR AT PUBLIC HALL, 1st STORY |
| Mar 30, 2022 | B | FIRST NO ACCESS TO RE- INSPECT VIOLATION | Not available | § 27-2040 ADM CODE PROVIDE ADEQUATE LIGHTING AT OR NEAR THE OUTSIDE OF THE FRONT ENTRANCEWAY OF THE BUILDING AND KEEP SAME BURNING FROM SUNSET EVERY DAY TO SUNRISE ON THE DAY FOLLOWING 100 WATTS INCAND. MINIMUM REQUIRED |
| Mar 30, 2022 | A | VIOLATION CLOSED | Not available | § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL WALLS AND CEILINGS ALL STORIES AT PUBLIC HALL |
| Mar 30, 2022 | B | VIOLATION CLOSED | Not available | § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTE AT ALL WALLS 1ST AND 2ND STIRIES AT PUBLIC HALL |
| Mar 30, 2022 | C | VIOLATION CLOSED | Not available | § 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE DOOR FRAME AT FRONT ENTRANCE TO BUILDING |
| Mar 30, 2022 | C | VIOLATION CLOSED | Not available | § 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE AT FRONT ENTRANCE TO BUILDING |
| Mar 23, 2022 | C | VIOLATION CLOSED | Not available | § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING ( 75 SQ FT ) THROUGHOUT AT CELLAR ORIGINAL VIOLATION 15073564 ISSUED 23-MAR-22 HAS BEEN UPGRADED TO CLASS C PER ADMINISTRATIVE CODE §27-2017.3a(5)(a) or (b). |
| Mar 23, 2022 | B | NOT COMPLIED WITH | Not available | § 27-2050 ADM CODE PROVIDE A PIECE OF GARDEN HOSE 10 FEET IN LENGTH WITH FEMALE COUPLING AND A 10 QUART PAIL ON PREMISES TO TEST SPRINKLER SYSTEM. |
| Mar 23, 2022 | B | VIOLATION CLOSED | Not available | § 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE REAR YARD |
| Mar 23, 2022 | B | FIRST NO ACCESS TO RE- INSPECT VIOLATION | Not available | § 27-2040 ADM CODE INSTALL AND MAINTAIN SUFFICIENT LIGHT OR LIGHTS OF AT LEAST 100 WATTS INCANDESCENT OR EQUIVALENT EACH, TO LIGHT ADEQUATELY FROM SUNSET TO SUNRISE THE REAR YARD |
| Mar 23, 2022 | A | VIOLATION CLOSED | Not available | § 27-2005 ADM CODE REFIT THE BUILDING FRONT ENTRANCE DOOR |
| Mar 23, 2022 | C | VIOLATION CLOSED | Not available | § 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE AT THE BUILDING FRONT ENTRANCE |
| Mar 23, 2022 | C | VIOLATION CLOSED | Not available | § 27-2005 ADM CODE PROPERLY SECURE THE LOOSE NORTH HANDRAIL AT STAIRS AT CELLAR |
| Mar 23, 2022 | B | VIOLATION CLOSED | Not available | § 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE DOOR FRAME AT BOILER ROOM |
| Mar 23, 2022 | C | VIOLATION CLOSED | Not available | § 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE .. AT BOILER ROOM |
| Mar 23, 2022 | B | NOT COMPLIED WITH | Not available | § 27-2050 ADM CODE SEAL IN OPEN POSITION THE O.S.Y. VALVE OF THE SPRINKLER SYSTEM IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THIS DEPARTMENT NOT SEALED ON OPEN POSITION AT CELLAR |
| Mar 23, 2022 | B | NOT COMPLIED WITH | Not available | § 27-2050 ADM CODE PROVIDE 3 EXTRA SPRINKLER HEADS AND SUITABLE WRENCH FOR EMERGENCY PURPOSES AT O.S.Y. VALVE OF SPRINKLER IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THIS DEPARTMENT MISSING AT CELLAR |
| Mar 23, 2022 | B | VIOLATION CLOSED | Not available | § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER ON SOUTH WALL THROUGHOUT AT CELLAR |
| Mar 23, 2022 | B | VIOLATION CLOSED | Not available | § 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRIC WIRES AT CEILING THROUGHOUT AT CELLAR |
| Mar 23, 2022 | B | VIOLATION CLOSED | Not available | § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING ( 75 SQ FT ) THROUGHOUT AT CELLAR |
| Mar 23, 2022 | C | VIOLATION CLOSED | Not available | § 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE UPPER SASH GLASS ON 1ST. WINDOW FROM SOUTH AT WEST AT THE BUILDING FRONT. , 1st STORY |
| Mar 23, 2022 | B | VIOLATION CLOSED | 2 | § 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRIC WIRES AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 2, 2nd STORY, APARTMENT AT NORTH |
| Mar 23, 2022 | B | VIOLATION CLOSED | 2 | § 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE SINK CABINET IN THE KITCHEN LOCATED AT APT 2, 2nd STORY, APARTMENT AT NORTH |
| Mar 10, 2022 | A | FIRST NO ACCESS TO RE- INSPECT VIOLATION | Not available | (A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS. |
| Oct 20, 2021 | B | VIOLATION CLOSED | Not available | § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER AT SOUTH WALL AT PUBLIC HALL, 1st STORY |
| Oct 20, 2021 | B | NOT COMPLIED WITH | Not available | § 27-2050 ADM CODE PROVIDE A PIECE OF GARDEN HOSE 10 FEET IN LENGTH WITH FEMALE COUPLING AND A 10 QUART PAIL ON PREMISES TO TEST SPRINKLER SYSTEM. |
| Oct 20, 2021 | B | NOT COMPLIED WITH | Not available | § 27-2050 ADM CODE PROVIDE 3 EXTRA SPRINKLER HEADS AND SUITABLE WRENCH FOR EMERGENCY PURPOSES AT O.S.Y. VALVE OF SPRINKLER IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THIS DEPARTMENT .. AT CELLAR |
| Oct 20, 2021 | B | VIOLATION CLOSED | Not available | § 27-2050 ADM CODE SEAL IN OPEN POSITION THE O.S.Y. VALVE OF THE SPRINKLER SYSTEM IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THIS DEPARTMENT .. AT CELLAR |
| Oct 20, 2021 | C | VIOLATION CLOSED | Not available | § 27-2005, 2007, 204.1 HMC CODE: ARRANGE AND MAKE SELF-CLOSING THE DOORS TO BOILER ROOM AT CELLAR |
| Oct 20, 2021 | C | VIOLATION CLOSED | Not available | § 27-2005, 2007, 204.1 HMC CODE: ARRANGE AND MAKE SELF-CLOSING THE DOORS AT FRONT ENTRANCE TO BUILDING |
| Oct 20, 2021 | C | VIOLATION CLOSED | Not available | § 27-2005 ADM CODE REPLACE WITH NEW THE MISSING SCUTLE COVER TO ROOF AT PUBLIC HALL, 3rd STORY |
| Oct 20, 2021 | C | VIOLATION CLOSED | 2 | § 27-2005, 2007, 204.1 HMC CODE: ARRANGE AND MAKE SELF-CLOSING THE DOORS .. IN THE ENTRANCE LOCATED AT APT 2, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Oct 20, 2021 | B | VIOLATION CLOSED | 2 | § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 2, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Oct 20, 2021 | B | VIOLATION CLOSED | 2 | § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 2, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Oct 20, 2021 | B | VIOLATION CLOSED | 2 | § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 2, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Oct 20, 2021 | B | VIOLATION CLOSED | 2 | § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 2, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Sep 30, 2021 | B | VIOLATION DISMISSED | Not available | § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS AND CEILING AT PUBLIC HALL, 1st STORY |
| Sep 30, 2021 | C | VIOLATION DISMISSED | Not available | § 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM AT PUBLIC HALL, 1st STORY |
| Sep 30, 2021 | A | VIOLATION DISMISSED | Not available | § 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY |