| Date | Class | Status | Apartment | Summary |
|---|---|---|---|---|
| Dec 11, 2019 | C | VIOLATION CLOSED | 3FLOOR | § 27-2005 ADMIN. CODE: REPLACE WITH NEW THE BROKEN OR DEFECTIVE AIR VALVES TO RADIATORS IN THE ENTIRE APARTMENT LOCATED AT APT 3FLOOR, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Dec 7, 2019 | A | VIOLATION CLOSED | 2 | § 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER WINDOW SASH AT SOUTH WALL IN THE 3rd ROOM FROM EAST LOCATED AT APT 2, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Nov 3, 2019 | B | VIOLATION CLOSED | TOPFLO | § 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT TOPFLO, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Nov 3, 2019 | C | VIOLATION DISMISSED | TOPFLO | § 27-2031 ADMIN. CODE: PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT TOPFLO, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Feb 23, 2019 | C | VIOLATION DISMISSED | TOPFL | § 27-2029 ADMIN. CODE: PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT TOPFL, 3rd STORY |
| Feb 22, 2019 | B | VIOLATION CLOSED | 2FLR | § 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILING AND ALL WALLS IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 2FLR, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Feb 22, 2019 | B | VIOLATION CLOSED | 2FLR | § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 2FLR, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Feb 15, 2019 | B | VIOLATION CLOSED | TOP | § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS AND CEILINGS IN THE ENTIRE APARTMENT LOCATED AT APT TOP, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Feb 15, 2019 | I | VIOLATION DISMISSED | Not available | §27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID REGISTRATION STATEMENT IS FILED. |
| Feb 14, 2019 | B | VIOLATION CLOSED | 2NDFL | § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK NORTH WALL AND CEILING IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 2NDFL, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Feb 14, 2019 | B | VIOLATION CLOSED | 2NDFL | § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK SOUTH WALL IN THE 3rd ROOM FROM EAST LOCATED AT APT 2NDFL, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Feb 14, 2019 | B | VIOLATION CLOSED | 2NDFL | § 27-2026 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE CONNECTION AT RADIATOR AT NORTH WALL IN THE 5th ROOM FROM EAST LOCATED AT APT 2NDFL, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Feb 14, 2019 | B | VIOLATION CLOSED | 2NDFL | § 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR NORTH WALL AND CEILING AT EAST-SOUTH 1 ROOM IN THE 5th ROOM FROM EAST LOCATED AT APT 2NDFL, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Feb 14, 2019 | B | VIOLATION CLOSED | 2NDFL | § 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR SOUTH WALL AT LIVING ROOM E 3 IN THE 5th ROOM FROM EAST LOCATED AT APT 2NDFL, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH |
| Feb 13, 2019 | C | VIOLATION CLOSED | TOPFL | § 27-2029 ADMIN. CODE: PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT TOPFL, 2nd STORY |
| Feb 13, 2019 | A | VIOLATION CLOSED | TOPFL | § 27-2005 ADMIN. CODE: REFIT THE TOP WINDOW SASH IN THE 3rd ROOM FROM EAST LOCATED AT APT TOPFL, 2nd STORY |
| Feb 13, 2019 | B | VIOLATION CLOSED | TOPFL | § 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR THE SOUTH WALL IN THE 2nd ROOM FROM EAST LOCATED AT APT TOPFL, 2nd STORY |
| Feb 13, 2019 | B | VIOLATION CLOSED | TOPFL | § 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT TOPFL, 2nd STORY |
| Feb 13, 2019 | B | VIOLATION CLOSED | TOPFL | § 27-2005 ADMIN. CODE: REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT TOPFL, 2nd STORY |
| Feb 12, 2019 | B | DEFECT LETTER ISSUED | FL2 | § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING 6SQ.FT IN THE BATHROOM LOCATED AT APT FL2, 3rd STORY ORIGINAL VIOLATION 12907799 ISSUED 12-FEB-19 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Feb 12, 2019 | B | DEFECT LETTER ISSUED | FL2 | § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING 4 SQ.FT, AND NORTH WALL 2 SQ.FT IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT FL2, 3rd STORY ORIGINAL VIOLATION 12907794 ISSUED 12-FEB-19 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Feb 12, 2019 | B | DEFECT LETTER ISSUED | FL2 | § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT SOUTH WALL 8 SQ.FT IN THE 2nd ROOM FROM EAST LOCATED AT APT FL2, 3rd STORY ORIGINAL VIOLATION 12907754 ISSUED 12-FEB-19 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b). |
| Feb 12, 2019 | A | VIOLATION CLOSED | Not available | § 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED |
| Feb 12, 2019 | A | VIOLATION CLOSED | Not available | § 27-2013 ADMIN. CODE: PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE SOUTH WALL AT PUBLIC HALL, 3rd STORY |
| Feb 12, 2019 | B | VIOLATION CLOSED | Not available | § 27-2005 ADMIN. CODE: PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER AT SOUTH WALL AT PUBLIC HALL, 3rd STORY |
| Feb 12, 2019 | B | VIOLATION CLOSED | FL2 | § 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE SPRING BALANCES UPPER WINDOW SASH IN THE 2nd ROOM FROM EAST LOCATED AT APT FL2, 3rd STORY |
| Feb 12, 2019 | B | VIOLATION CLOSED | FL2 | § 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE SPRING BALANCES LOWER WINDOW SASH IN THE 4th ROOM FROM EAST LOCATED AT APT FL2, 3rd STORY |
| Feb 12, 2019 | A | VIOLATION CLOSED | FL2 | § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING 6SQ.FT IN THE BATHROOM LOCATED AT APT FL2, 3rd STORY |
| Feb 12, 2019 | B | VIOLATION CLOSED | FL2 | § 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILING AND NORTH WALL IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT FL2, 3rd STORY |
| Feb 12, 2019 | A | VIOLATION CLOSED | FL2 | § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING 4 SQ.FT, AND NORTH WALL 2 SQ.FT IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT FL2, 3rd STORY |
| Feb 12, 2019 | A | VIOLATION CLOSED | FL2 | § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT SOUTH WALL 8 SQ.FT IN THE 2nd ROOM FROM EAST LOCATED AT APT FL2, 3rd STORY |
| Feb 12, 2019 | B | VIOLATION CLOSED | FL2 | § 27-2005 ADMIN. CODE: REPAIR THE ROOF SO THAT IT WILL NOT LEAK CEILING IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT FL2, 3rd STORY |
| Feb 12, 2019 | A | VIOLATION CLOSED | FL2 | § 27-2013 ADMIN. CODE: PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT STEAM RISER IN THE BATHROOM LOCATED AT APT FL2, 3rd STORY |
| Feb 5, 2019 | C | VIOLATION CLOSED | Not available | § 27-2005 ADMIN. CODE: PROPERLY SECURE THE LOOSE SCUTTLE LADDER AT PUBLIC HALL, 3rd STORY |
| Feb 5, 2019 | A | VIOLATION CLOSED | Not available | § 27-2013 ADMIN. CODE: PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL WALLS AND CEILING AT PUBLIC HALL, 3rd STORY |
| Feb 5, 2019 | B | VIOLATION CLOSED | Not available | § 27-2005 ADMIN. CODE: PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLATSTER CEILING AND WEST WALL AT PUBLIC HALL, 3rd STORY |
| Feb 5, 2019 | B | VIOLATION CLOSED | TOPFL | § 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE LOCATED AT APT TOPFL, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Feb 5, 2019 | B | VIOLATION CLOSED | TOPFL | § 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT TOPFL, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Feb 5, 2019 | B | VIOLATION CLOSED | TOPFL | § 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE LOWER WINDOW SASH 1ST FROM WEST AT SOUTH WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT TOPFL, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Feb 5, 2019 | B | VIOLATION CLOSED | TOPFL | § 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR AT CEILING IN THE 3rd ROOM FROM NORTH LOCATED AT APT TOPFL, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Feb 5, 2019 | B | VIOLATION CLOSED | TOPFL | § 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR AT CEILING IN THE 3rd ROOM FROM NORTH AT EAST LOCATED AT APT TOPFL, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST |
| Mar 16, 2006 | C | VIOLATION CLOSED | 3FL | § 27-2005 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF SCALDING HOT WATER TEMPERATURE IN THE ENTIRE APARTMENT LOCATED AT APT 3FL, 3rd STORY |