Brooklyn Fort Greene
DOB violations
Department of Buildings violations attached to this BIN or tax lot.
83 records
| Date | Status | Type | Summary |
|---|---|---|---|
| Aug 25, 2026 | V-DOB VIOLATION - ACTIVE | C-CONSTRUCTION OTHER OPTIONAL | FTM. OBSERVED ON EXP 1 WEST ELEVATION:- CRACKS IN MASONRY PARAPET ON THE 13 FL SETBACK. MISSING MASONRY LINTEL ON 9TH FL. EXP 2 NORTH ELEVATION:- CRACK ON 13 FLOOR; MISSING SECTION OF MASONRY ON 13 FLOOR LOOSE, MISSING COPING STONE MORTAR JOINTS ON 13TH FLOOR SETBACK REMEDY: REPAIR AND/OR REPLACE, ALL DEFECTIVE CONDITIONS |
| Feb 6, 2026 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. CEASE USE ORDER ISSUED FOR THE FOLLOWING ITEM: DAMAGE TO ELECTRONIC COMPONENTS AS A RESULT OF FLOODING. |
| Nov 6, 2025 | V-DOB VIOLATION - ACTIVE | C-CONSTRUCTION OTHER OPTIONAL | FAILURE TO BUILDING IN A CODE COMPLIANT MANNER. OBSERVED OPEN SECTIONS OF STONE WORK ON EXPOSURE 1 AND 2. REMEDY: REPAIR AND OR REPLACE |
| Apr 28, 2025 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. CEASE USE ORDER ISSUED FOR THE FOLLOWING ITEM: DAMAGE TO ELECTRONIC COMPONENTS AS A RESULT OF FLOODING. |
| Feb 11, 2025 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. CEASE USE ORDER ISSUED FOR THE FOLLOWING ITEM: DAMAGE TO ELECTRONIC COMPONENTS AS A RESULT OF FLOODING. |
| Oct 17, 2024 | V*-DOB VIOLATION - DISMISSED | IMEGNCY-IMMEDIATE EMERGENCY ANYTHINGOPTIONAL | REPAIR THE SWS PARAPET WALL PANELS AND PLANKING AS PER CODE TO SAFE GUARD THE PUBLIC AND PROPERTY |
| Oct 16, 2024 | V-DOB VIOLATION - ACTIVE | C-CONSTRUCTION OTHER OPTIONAL | STRUCTURE RENDERED NON COMPLIANT . AT TIME OF INSPECTION OBSERVED A T OP SIDEWALK SHED PLANKING DAMAGED & MOVED DUE TI FIRE . SECTION OF PARAPET ALSO DAMAGED AT EXPOSURE 1 SECTION MISSING AND ALSO LEAING OUTWARD. STRUCTURE MUST BE MAINTAINED IN A CODE COMPLIANT MANNER |
| Jul 5, 2024 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | WATER DAMAGE TO ELEVATOR FROM 10TH FLOOR DOWN. WATER AFFECTED THE CAR TOP INSPECTION STATION, ESCAPE HATCH SAFETY SWITCH, CAR STATION, DOOR LOCKS, DOOR OPERATOR, PIT LIMIT SWITCHES AND STOP SWITCHES. THE TRAVELER AND CAB WALLS HAVE UNDETERMINED DAMAGED WHICH WILL BE ASSESSED BY ELEVATOR COMPANY FOR POTENTIAL REPLACEMENT (CEASE USE) |
| Jul 5, 2024 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | WATER DAMAGE TO ELEVATOR FROM 10TH FLOOR DOWN. WATER AFFECTED THE CAR TOP INSPECTION STATION, ESCAPE HATCH SAFETY SWITCH, CAR STATION, DOOR LOCKS, DOOR OPERATOR, PIT LIMIT SWITCHES AND STOP SWITCHES. THE TRAVELER AND CAB WALLS HAVE UNDETERMINED DAMAGED WHICH WILL BE ASSESSED BY ELEVATOR COMPANY FOR POTENTIAL REPLACEMENT. (CEASE USE) |
| Jun 30, 2023 | V*-DOB VIOLATION - DISMISSED | LBLVIO-LOW PRESSURE BOILER BOILER REQUIRED | VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION |
| Apr 25, 2023 | V*-DOB VIOLATION - DISMISSED | LBLVIO-LOW PRESSURE BOILER BOILER REQUIRED | VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION |
| Apr 25, 2023 | V*-DOB VIOLATION - DISMISSED | LBLVIO-LOW PRESSURE BOILER BOILER REQUIRED | VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION |
| Apr 25, 2023 | V*-DOB VIOLATION - DISMISSED | LBLVIO-LOW PRESSURE BOILER BOILER REQUIRED | VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION |
| Apr 25, 2023 | V*-DOB VIOLATION - DISMISSED | LBLVIO-LOW PRESSURE BOILER BOILER REQUIRED | VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION |
| Apr 25, 2023 | V*-DOB VIOLATION - DISMISSED | LBLVIO-LOW PRESSURE BOILER BOILER REQUIRED | VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION |
| Apr 25, 2023 | V*-DOB VIOLATION - DISMISSED | LBLVIO-LOW PRESSURE BOILER BOILER REQUIRED | VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION |
| Apr 25, 2023 | V*-DOB VIOLATION - DISMISSED | LBLVIO-LOW PRESSURE BOILER BOILER REQUIRED | VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION |
| Apr 4, 2022 | V-DOB VIOLATION - ACTIVE | FISPHAZ-HAZARDOUS CONDITION (FACADE) FACADE REQUIRED | CYCLE 9C UNSAFE REPORT FILED |
| Dec 17, 2021 | V*-DOB VIOLATION - DISMISSED | EVCAT5-NON-RESIDENTIAL ELEVATOR PERIODIC INSPECTION/TEST ELEVATORREQUIRED | FAILURE TO PERFORM CATEGORY 5 INSPECTION |
| Dec 17, 2021 | V*-DOB VIOLATION - DISMISSED | EVCAT5-NON-RESIDENTIAL ELEVATOR PERIODIC INSPECTION/TEST ELEVATORREQUIRED | FAILURE TO PERFORM CATEGORY 5 INSPECTION |
| Aug 27, 2021 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | E-ELEVATOR ELEVATORREQUIRED |
| Aug 27, 2021 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | E-ELEVATOR ELEVATORREQUIRED |
| Jun 16, 2021 | V-DOB VIOLATION - ACTIVE | C-CONSTRUCTION OTHER OPTIONAL | FAILURE TO COMPLY-ON 8/13/2020, COMMISSIONERS ORDER 349415 DIRECTED RETAINING SERVICES OF NYS REG. DESIGN W/STUCCO EXPERIENCE TO INSPECT 100% STUCCO ELEMENTS HANDS ON SOUND ALL EXPOSURES TO DETERMINE SAFETY OF SAME & CAUSE FAILURE. SAME PROF TO CREATE A REPORT. REMEDY: IMMED COMPLY WITH CODE AND COMMISSIONERS ORDER |
| Mar 3, 2021 | V*-DOB VIOLATION - DISMISSED | AEUHAZ1-FAIL TO CERTIFY CLASS 1 NONE | FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION |
| Feb 21, 2021 | V-DOB VIOLATION - ACTIVE | FISPFCS-FAILURE TO CORRECT SWARMP CONDITIONS (FACADE) FACADE REQUIRED | CYCLE 8C FAILURE TO CORRECT SWARMP CONDITIONS |
| Aug 13, 2020 | V-DOB VIOLATION - ACTIVE | C-CONSTRUCTION OTHER OPTIONAL | FTM FACADE AND APPURTENANCES. UNSAFE FISP REPORT WAS SUBMITTED BY JAY BUTLER, PE ON 2/21/2020. THE QEWI STATES THAT A SECTION OF STUCCO MATERIAL WAS DISPLACED FROM EXP 3(EAST FACADE)AND FELL INTO THE PARKING LOT ON 3/2019. REMEDY:OWNER TO IMMED. RETAIN SERVICES OF NYS REGISTERED DESIGN PROF WITH STUCCO EXPERIENCE TO INSP AND EVAL 100% |
| Jul 13, 2020 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | E-ELEVATOR ELEVATORREQUIRED |
| Jul 13, 2020 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | E-ELEVATOR ELEVATORREQUIRED |
| Jul 13, 2020 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | E-ELEVATOR ELEVATORREQUIRED |
| Jul 13, 2020 | V-DOB VIOLATION - ACTIVE | E-ELEVATOR ELEVATORREQUIRED | E-ELEVATOR ELEVATORREQUIRED |
| Jul 13, 2020 | V-DOB VIOLATION - ACTIVE | E-ELEVATOR ELEVATORREQUIRED | E-ELEVATOR ELEVATORREQUIRED |
| Feb 21, 2020 | V-DOB VIOLATION - ACTIVE | FISPHAZ-HAZARDOUS CONDITION (FACADE) FACADE REQUIRED | FISPHAZ-HAZARDOUS CONDITION (FACADE) FACADE REQUIRED |
| Nov 8, 2019 | V*-DOB VIOLATION - DISMISSED | LBLVIO-LOW PRESSURE BOILER BOILER REQUIRED | VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT |
| Aug 3, 2019 | V*-DOB VIOLATION - DISMISSED | BENCH-FAILURE TO BENCHMARK NONE | FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4 |
| Jul 12, 2019 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | E-ELEVATOR ELEVATORREQUIRED |
| Jul 12, 2019 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | E-ELEVATOR ELEVATORREQUIRED |
| Jul 12, 2019 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | E-ELEVATOR ELEVATORREQUIRED |
| May 2, 2019 | V*-DOB VIOLATION - DISMISSED | BENCH-FAILURE TO BENCHMARK NONE | FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4 |
| Apr 30, 2019 | V*-DOB VIOLATION - DISMISSED | FISPNRF-NO REPORT AND / OR LATE FILING (FACADE) FACADE REQUIRED | FAILED TO FILE FISP CYCLE 8C TECHNICAL REPORT BY 02/21/2019 |
| Feb 16, 2019 | V*-DOB VIOLATION - DISMISSED | BENCH-FAILURE TO BENCHMARK NONE | FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4 |
| Feb 2, 2018 | V*-DOB VIOLATION - DISMISSED | BENCH-FAILURE TO BENCHMARK NONE | FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4 |
| Nov 2, 2017 | V*-DOB VIOLATION - DISMISSED | BENCH-FAILURE TO BENCHMARK NONE | FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4 |
| Aug 2, 2017 | V*-DOB VIOLATION - DISMISSED | BENCH-FAILURE TO BENCHMARK NONE | FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4 |
| Jun 13, 2017 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | E-ELEVATOR ELEVATORREQUIRED |
| Jun 13, 2017 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | E-ELEVATOR ELEVATORREQUIRED |
| May 2, 2017 | V*-DOB VIOLATION - DISMISSED | BENCH-FAILURE TO BENCHMARK NONE | FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4 |
| Apr 27, 2015 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | E-ELEVATOR ELEVATORREQUIRED |
| Apr 27, 2015 | V*-DOB VIOLATION - Resolved | E-ELEVATOR ELEVATORREQUIRED | E-ELEVATOR ELEVATORREQUIRED |
| Dec 31, 2013 | V*-DOB VIOLATION - DISMISSED | FISPNRF-NO REPORT AND / OR LATE FILING (FACADE) FACADE REQUIRED | FAILED TO FILE FISP CYCLE 7C TECHNICAL REPORT BY 02/21/2013 |
| Jun 19, 2013 | V*-DOB VIOLATION - DISMISSED | AEUHAZ1-FAIL TO CERTIFY CLASS 1 NONE | FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION |