Housing Maintenance Code violations are filed by tax lot (BBL 3-04519-0118), so they can include other buildings on the same lot.

302 records

Date Class Status Apartment Summary
Dec 1, 2021 A VIOLATION CLOSED 3 § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROXIMATELY 9SQ.FT AT CEILING AT THE CLOSET AT SOUTH WALL IN THE PRIVATE HALLWAY LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Dec 1, 2021 A VIOLATION CLOSED 3 § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROXIMATELY 2SQ.FT AT CEILING IN THE KITCHEN LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Dec 1, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE CEILING IN THE KITCHEN LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Dec 1, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE KITCHEN LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Dec 1, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE KITCHEN LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Nov 13, 2021 B NOV SENT OUT Not available § 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES AT CEILING AT PUBLIC HALL, 1st STORY
Nov 13, 2021 C NOTICE OF ISSUANCE SENT TO TENANT 1 HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Nov 13, 2021 C NOTICE OF ISSUANCE SENT TO TENANT 1 HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Nov 1, 2021 B FIRST NO ACCESS TO RE- INSPECT VIOLATION 3 § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT THE CEILING AND EAST WALL IN THE BATHROOM IN THE 2nd ROOM FROM EAST LOCATED AT APT 3, 3rd STORY ORIGINAL VIOLATION 14659142 ISSUED 01-NOV-21 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Nov 1, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE AIR VENT AT THE CEILING IN THE FOYER LOCATED AT APT 3, 3rd STORY
Nov 1, 2021 B NOV SENT OUT 3 § 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY
Nov 1, 2021 A VIOLATION CLOSED 3 § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT THE CEILING AND EAST WALL IN THE BATHROOM IN THE 2nd ROOM FROM EAST LOCATED AT APT 3, 3rd STORY
Nov 1, 2021 B NOV SENT OUT 3 § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT THE CEILING AND EAST WALL IN THE BATHROOM IN THE 2nd ROOM FROM EAST LOCATED AT APT 3, 3rd STORY
Nov 1, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE KITCHEN LOCATED AT APT 3, 3rd STORY
Nov 1, 2021 B NOV SENT OUT 3 § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT THE CEILING IN THE KITCHEN LOCATED AT APT 3, 3rd STORY
Nov 1, 2021 C VIOLATION CLOSED 3 § 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES AT THE CEILINGS AND WALLS IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY
Nov 1, 2021 B NOV SENT OUT Not available § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AT PUBLIC HALL, 3rd STORY
Nov 1, 2021 B NOV SENT OUT Not available § 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING AT PUBLIC HALL, 3rd STORY
Nov 1, 2021 A NOV SENT OUT 3 § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CLOSET CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Nov 1, 2021 B FIRST NO ACCESS TO RE- INSPECT VIOLATION 3 § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CLOSET CEILING.APPROX. 10 SQ FT. IN THE 1st ROOM FROM EAST LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Nov 1, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Nov 1, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING. IN THE 1st ROOM FROM EAST LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Nov 1, 2021 A NOV SENT OUT 3 § 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE INOPERATIVE BELL AND RETURN BUZZER SYSTEM AT FRONT BUILDING TO IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Nov 1, 2021 C VIOLATION CLOSED 3 § 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE . IN THE ENTRANCE LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Nov 1, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR A CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Nov 1, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Nov 1, 2021 C VIOLATION CLOSED 3 § 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES .. IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Nov 1, 2021 B NOV SENT OUT 3 § 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Nov 1, 2021 B NOV SENT OUT 3 § 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 C VIOLATION CLOSED 3 § 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE , IN THE ENTRANCE LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 B NOV SENT OUT 3 § 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR INOPERATIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 B NOV SENT OUT 3 § 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). INOPERATIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 C VIOLATION DISMISSED 3 § 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE CEILING IN THE CLOSET IN THE 1st ROOM FROM EAST LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS AND CEILING AT THE CLOSET IN THE 1st ROOM FROM EAST LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS AND CEILING AT THE CLOSET IN THE 1st ROOM FROM EAST LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK MOISTURE PENETRATING OVER THE WALLS AT CLOSET IN THE 1st ROOM FROM EAST LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 B NOV SENT OUT 3 § 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRICAL WIRE AT THE CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 C VIOLATION DISMISSED 3 § 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE CEILING AND SOUTH WALL IN THE PRIVATE HALLWAY LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 A NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE WALLS IN THE PRIVATE HALLWAY LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 C VIOLATION CLOSED 3 § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK MOISTURE PENETRATING OVER THE NORTH AND EAST WALLS, IN THE BATHROOM IN THE 2nd ROOM FROM NORTH AT WEST LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 C VIOLATION DISMISSED 3 § 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE CEILING AND SOUTH WALL IN THE 2nd ROOM FROM NORTH AT WEST LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE WALLS AND CEILING AT BATHROOM IN THE 2nd ROOM FROM NORTH AT WEST LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 14, 2021 C VIOLATION CLOSED 3 § 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES ALL ELECTRICAL FIXTURES AND OUTLETS IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 12, 2021 B FIRST NO ACCESS TO RE- INSPECT VIOLATION 3 § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... (APPROX 4 SQ FT) ON CEILING IN THE 2nd BATHROOM FROM EAST AT SOUTH LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH ORIGINAL VIOLATION 14613806 ISSUED 12-OCT-21 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Oct 12, 2021 B FIRST NO ACCESS TO RE- INSPECT VIOLATION 3 § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... (APPROX 6 SQ FT) ON CEILING AT THE SOUTH CLOSET IN THE FOYER LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH ORIGINAL VIOLATION 14613802 ISSUED 12-OCT-21 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Oct 12, 2021 C NOV SENT OUT Not available § 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM AT PUBLIC HALL, 1st STORY
Oct 12, 2021 C NOV SENT OUT Not available § 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM BOILER ROOM DOOR LOCKED AT CELLAR
Oct 12, 2021 C VIOLATION CLOSED 3 § 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Oct 12, 2021 B NOV SENT OUT 3 § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE SOUTH WALL IN THE KITCHENETTE LOCATED AT APT 3, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH