Housing Maintenance Code violations are filed by tax lot (BBL 3-06681-0399), so they can include other buildings on the same lot.

597 records

Date Class Status Apartment Summary
Feb 15, 2026 C VIOLATION DISMISSED Not available § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER AT CEILING AT 2nd PUBLIC HALL FROM NORTH, 1st STORY
Feb 15, 2026 C VIOLATION CLOSED Not available § 27-2005, 2007 ADM CODE REMOVE DEVICE PREVENTING DOOR FROM BEING SELF-CLOSING CONSISTING OF WOOD WEDGE PLACED AT FIRE DOOR AT 2nd PUBLIC HALL FROM NORTH, 2nd STORY
Feb 13, 2026 B VIOLATION DISMISSED Not available § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDENT MATERIALS AT EAST WALL AT PUBLIC HALL, 1st STORY
Jan 12, 2026 C VIOLATION CLOSED Not available § 27-2005, 2007 ADM CODE REMOVE DEVICE PREVENTING DOOR FROM BEING SELF-CLOSING CONSISTING OF A DOOR WEDGE AT FIRE RATED PARTITION DOOR AT PUBLIC HALL, 4th STORY
Nov 21, 2025 B VIOLATION DISMISSED D5 § 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT D5, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
Nov 21, 2025 B VIOLATION DISMISSED D5 § 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT D5, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
Nov 18, 2025 C VIOLATION CLOSED E5 § 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF UPPER CABINET AND LOWER CABINET ISLAND AT EAST WALL BLOCKING FIRE EXIT DOOR TO SOUTH SECTION OF THE BUILDING IN THE KITCHEN LOCATED AT APT E5, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''NORTH''
Nov 18, 2025 B VIOLATION DISMISSED E5 § 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT E5, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''NORTH''
Nov 18, 2025 B VIOLATION DISMISSED E5 § 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT E5, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''NORTH''
Oct 30, 2025 B VIOLATION DISMISSED B5 § 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Oct 30, 2025 B VIOLATION DISMISSED B5 § 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES INOPERABLE IN THE ENTIRE APARTMENT LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 B FIRST NO ACCESS TO RE- INSPECT VIOLATION B5 § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ.FT AT EAST WALL IN THE BATHROOM LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 18226744 ISSUED 14-SEP-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
Sep 14, 2025 B FIRST NO ACCESS TO RE- INSPECT VIOLATION B5 § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ.FT AT WEST WALL IN THE 4th ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 18226735 ISSUED 14-SEP-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
Sep 14, 2025 A VIOLATION DISMISSED B5 § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE 1st DOOR FRAME FROM NORTH AT EAST WALL, SOUTH WALL IN THE 4th ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 A VIOLATION DISMISSED B5 § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE 1st DOOR FRAME FROM NORTH AT EAST WALL, SOUTH WALL IN THE 4th ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 C FIRST NO ACCESS TO RE- INSPECT VIOLATION B5 § 27-2056.7, 27-2056.8, 27-2056.9 ADM CODE -CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY PERFORMING ACTIVITIES NECESSARY TO ABATE TESTED LEAD-BASED PAINT FROM REQUIRED WINDOW AND/OR DOOR FRICTION SURFACES FOR APARTMENT AND MAKE FLOORS SMOOTH AND CLEANABLE, POSITIVE LEAD-BASED PAINT IN AN APARTMENT WITH A CHILD UNDER SIX LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 C VIOLATION CLOSED B5 § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD-PAINT THAT IS XRF TESTED INCONCLUSIVE FOR LEAD CONTENT AT 0.5MG/CM2 AND IS PRESUMED LEAD PAINT AS SET FORTH IN (28 RCNY §11-07(b)) AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE-USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(b)(2) 1st DOOR FRAME FROM NORTH AT EAST WALL, SOUTH WALL IN THE 4th ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 C VIOLATION CLOSED B5 § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 2nd WINDOW FRAME FROM EAST AT SOUTH WALL IN THE 4th ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 C VIOLATION CLOSED B5 § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM NORTH AT EAST WALL IN THE KITCHEN LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 C VIOLATION CLOSED B5 § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD-PAINT THAT IS XRF TESTED INCONCLUSIVE FOR LEAD CONTENT AT 0.5MG/CM2 AND IS PRESUMED LEAD PAINT AS SET FORTH IN (28 RCNY §11-07(b)) AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE-USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(b)(2) 1st DOOR FRAME FROM SOUTH AT WEST WALL, 2nd WINDOW FRAME FROM EAST AT SOUTH WALL IN THE 2nd ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 C VIOLATION CLOSED B5 § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD-PAINT THAT IS XRF TESTED INCONCLUSIVE FOR LEAD CONTENT AT 0.5MG/CM2 AND IS PRESUMED LEAD PAINT AS SET FORTH IN (28 RCNY §11-07(b)) AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE-USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(b)(2) 1st DOOR FRAME FROM SOUTH AT WEST WALL IN THE FOYER LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 C VIOLATION CLOSED B5 § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD-PAINT THAT IS XRF TESTED INCONCLUSIVE FOR LEAD CONTENT AT 0.5MG/CM2 AND IS PRESUMED LEAD PAINT AS SET FORTH IN (28 RCNY §11-07(b)) AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE-USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(b)(2) 1st DOOR FRAME FROM NORTH AT EAST WALL, SOUTH WALL IN THE 4th ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 C VIOLATION CLOSED B5 § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 2nd WINDOW FRAME FROM EAST AT SOUTH WALL IN THE 4th ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 C VIOLATION CLOSED B5 § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM NORTH AT EAST WALL IN THE KITCHEN LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 C VIOLATION CLOSED B5 § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD-PAINT THAT IS XRF TESTED INCONCLUSIVE FOR LEAD CONTENT AT 0.5MG/CM2 AND IS PRESUMED LEAD PAINT AS SET FORTH IN (28 RCNY §11-07(b)) AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE-USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(b)(2) 1st DOOR FRAME FROM SOUTH AT WEST WALL, 2nd WINDOW FRAME FROM EAST AT SOUTH WALL IN THE 2nd ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 C VIOLATION CLOSED B5 § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD-PAINT THAT IS XRF TESTED INCONCLUSIVE FOR LEAD CONTENT AT 0.5MG/CM2 AND IS PRESUMED LEAD PAINT AS SET FORTH IN (28 RCNY §11-07(b)) AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE-USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(b)(2) 1st DOOR FRAME FROM SOUTH AT WEST WALL IN THE FOYER LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 A VIOLATION DISMISSED B5 § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE BATHROOM , THE PRIVATE HALLWAY LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 A VIOLATION DISMISSED B5 § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT 1st WINDOW FRAME FROM EAST AT SOUTH WALL, CEILING, WEST WALL IN THE 4th ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 C NOV SENT OUT B5 § 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF APARTMENT ENTRANCE DOOR IS PAINTED SHOT AT EAST WALL IN THE KITCHEN LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 B NOV SENT OUT B5 § 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 B NOV SENT OUT B5 § 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 C VIOLATION DISMISSED B5 § 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 6, WG TO REPLACE = 0, WG TO REPAIR = 0 IN THE ENTIRE APARTMENT LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 A VIOLATION CLOSED B5 § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ.FT AT EAST WALL IN THE BATHROOM LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 B FIRST NO ACCESS TO RE- INSPECT VIOLATION B5 § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 30 SQ.FT AT WEST WALL IN THE BATHROOM LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 B FIRST NO ACCESS TO RE- INSPECT VIOLATION B5 § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 30 SQ.FT AT CEILING IN THE BATHROOM LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 B NOV SENT OUT B5 § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 A VIOLATION DISMISSED B5 § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT 1st CLOSET FROM NORTH AT EAST WALL DOOR, 1st DOOR FROM WEST AT NORTH WALL, 1st CLOSET FROM NORTH AT EAST WALL DOOR FRAME, 2nd DOOR FRAME FROM SOUTH AT WEST WALL IN THE FOYER LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 A VIOLATION CLOSED B5 § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ.FT AT WEST WALL IN THE 4th ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 B NOV SENT OUT B5 § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT WEST WALL IN THE 4th ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 B NOV SENT OUT B5 § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT SOUTH WALL IN THE 4th ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 B NOV SENT OUT B5 § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE 4th ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 B NOV SENT OUT B5 § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 4th ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 A VIOLATION DISMISSED B5 § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT 1st WINDOW FRAME FROM EAST AT SOUTH WALL IN THE 4th ROOM FROM EAST LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Sep 14, 2025 A VIOLATION DISMISSED B5 § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT 1st WINDOW FRAME FROM EAST AT SOUTH WALL IN THE KITCHEN LOCATED AT APT B5, 2nd STORY, 3rd APARTMENT FROM EAST AT SOUTH
Jul 17, 2025 B VIOLATION DISMISSED Not available § 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF BYCYCLES AT PUBLIC HALL, 3rd STORY
Jul 17, 2025 A NOV SENT OUT Not available § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT WEST WALL AT PUBLIC HALL, 6th STORY
Dec 11, 2024 C FALSE CERTIFICATION Not available § 27-2005, 2007 ADM CODE REMOVE DEVICE PREVENTING DOOR FROM BEING SELF-CLOSING CARDBOARD JAMMED AND OBSTRUCTED FIRE DOORS 1ST FROM NORTH AT EAST, AT PUBLIC HALL, 5th STORY
Sep 11, 2024 B NOV SENT OUT Not available § 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF FURNITURE AND STROLLERS AT PUBLIC HALL, 4th STORY
Sep 11, 2024 B NOV SENT OUT D4 § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING, NORTH, WEST AND EAST WALLS IN THE 4th ROOM FROM EAST LOCATED AT APT D4, 4th STORY, 5th APARTMENT FROM SOUTH AT WEST
Sep 11, 2024 A VIOLATION DISMISSED D4 § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT CEILING AND WEST WALL IN THE BATHROOM LOCATED AT APT D4, 4th STORY, 5th APARTMENT FROM SOUTH AT WEST